Technical Specifications
Manufacturer | Emerson |
Product No. | KJ3002X1-BA1 |
Product Type | Analog Input Module |
Model(s) | Emerson Delta V |
Dimensions | 1.5" x 4.0" x 4.5"(3.8 cm x 10.2 cm x 11.4 cm) |
Weight | 0 lbs 6.4 oz (0.2kg ) |
LocalBus power rating | 12 VDC at 150 mA |
More Information of EMERSON KJ3002X1-BA1 12P0680X072
Environmental Specifications | |
Ambient Temperature | 0 to 60°C |
Shock | 10g ½ Sinewave for 11 msec |
Vibration | 1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz |
Airborne Contaminants | ISA-S71.04 –1985 Airborne Contaminants Class G3 |
Relative Humidity | 5 to 95% Non-Condensing IP 20 Rating |
OverView | |
The Emerson KJ3002X1-BA1 (12P0680X072) is a high-performance 8-channel analog input module designed for industrial automation systems. Supporting 4-20 mA current loops and the HART protocol, this module ensures reliable signal acquisition from a variety of analog sensors. It operates on 12V bus power and is designed for 2-wire AI applications, making it ideal for process control in industries such as chemical, oil, gas, and manufacturing. This module offers seamless integration with Emerson DeltaV and Ovation systems. | |
Removal and Insertion | |
Field power supplied to this device, either at the field terminal or as bussed field power through the carrier, must be removed before removing or connecting the device. An I/O loop assessment must be complete on all energy limited nodes. This unit may be removed or inserted while system power is energized under the following conditions: (Note Only one unit at a time may be removed with system power energized.) When used with KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power. The primary circuit wiring inductance for input power must be less than 23 uH, or a certified supply with an open circuit voltage, Ui of 12.6 VDC and an Lo of less than 23 uH (including wire inductance). A rotary keying system ensures compatibility between I/O cards and terminal blocks after installation is complete. The terminal block must have the keys set for the I/O card with which it is to be used. A terminal block fuse may NOT be removed with field power energized for non-sparking circuits. | |
If you want to more details,please contact me without hesitate.Email:sales@sparecenter.com
Product Images

EMERSON KJ3002X1-BA1

EMERSON KJ3002X1-BA1

EMERSON KJ3002X1-BA1
Other Modules
EMERSONKJ3001X1-BJ1 12P0555X152DeltaV Digital Output Module EMERSONKJ3002X1-BA1 12P0680X122DeltaV Analog Input Module EMERSONKJ3002X1-BB1 12P0683X082DeltaV Analog Output Module EMERSON Analog Input Module EMERSON Analog Input Module EMERSON Analog Input Module EMERSON 12P0680X072 EMERSON 12P0680X072 EMERSON 12P0680X072 EMERSON 12P0680X072 EMERSONKJ3002X1-BG2 12P1731X062DeltaV Thermocouple MV Card EMERSONKJ3002X1-BA1 12P06801X122DeltaV Analog Input Module EMERSON Analog Input Module EMERSON Analog Input Module EMERSON Analog Input Module KJ3002X1-BA1 EMERSONKJ3002X1-BC1 12P0681X092DeltaV Analog Input Module EMERSONKJ3002X1-BE1 12P0682X052DeltaV Analog Output Module EMERSONKJ3002X1-BG2 12P1731X032DeltaV Thermocouple Module EMERSON 12P0680X072 EMERSON 12P0680X072 EMERSON 12P0680X072 EMERSON 12P0680X072 EMERSONPR6423/010-010 CON0218mm Eddy Current Sensor EMERSONKJ3243X1-BB1 12P3994X042 VE4022DeltaV Series 2 Plus Profibus DP Card EMERSONKJ2201X1-BA1 12P3162X162 SLS1508DeltaV Smart Logic Solver EMERSONA6560Processor Card EMERSONKJ3224X1-EA1 12P4367X022DeltaV Redundant Virtual I/O Module EMERSONKJ4001X1-NA1 12P3373X022LocalBus Dual Right Cable Extender EMERSONKJ4002X1-BF2 12P3866X012DeltaV Bottom Bus Extender Cable |
Mobile/what's app: +852 6980 6006
Email: sales@sparecenter.com