Specification
Environmental Specifications | Power Specifications | ||
Ambient Temperature | -40°C to +70°C | Local Bus Power | 24 VDC at 1 A |
Shock | 10g ½ Sinewave for 11msec | Field power | 4 A (maximum) |
Vibration | 1mm Peak to Peak from 2 to 13.2Hz; 0.7g from 13.2 to 150Hz | Input Power | 24 V DC ± 20%, 1.0 A plus field power (5.0 A total) |
Airborne Contaminants | ISA-S71.04 –1985 Airborne Contaminants Class G3 | Field Power | 4 A maximum |
Relative Humidity | 5 to 95% Non-Condensing |
Product details picture
If you want to more details,please contact me without hesitate.Email:sales@sparecenter.com
Product Information
Redundancy
The redundant SLS 1508 Logic Solver modules are connected to the field at the redundant terminal block. No control strategy configuration is required to take advantage of SLS 1508 Logic Solver redundancy, as the system’s auto-sense capability automatically recognizes the redundant pair of Logic Solvers. An integrity error alarm in a redundant SLS 1508 Logic Solver pair will notify the operator of a failure. Both SLS 1508 Logic Solvers in a redundant pair are monitored for integrity alarms at all times. Events that can cause integrity alarms include: Hardware failure within a SLS 1508 Logic Solver Communications failure between a SLS 1508 Logic Solver and the SISNet Communications failure between a redundant pair of SLS 1508 Logic Solvers Communications failure between a SLS 1508 Logic Solver and an DeltaV Controller Removal of a SLS 1508 Logic Solver from the carrier
Related Products
DeltaV Workstations and Server Hardware
DeltaV M-Series Traditional I/O
DeltaV SIS Hardware Carriers
DeltaV M-Series I/O Subsystem Horizontal Carriers
DeltaV VerticalPlus I/O Subsystem Carrier DeltaV PK Controller
DeltaV SIS with Electronic Marshalling
Prerequisites
DeltaV v8.3 software or later. VE4050E1C2 VE3051C0 The 2-wide power/controller carriers were upgraded in 2004 to accommodate the DeltaV SIS system. The new version of the 2-wide power/controller carrier has a small white rectangle printed on the board. This is visible between the power supply module and the MD Controller. The new part number is KJ4001X1-BA3 or higher. The old version had a white dot in place of the rectangle. The old version (with white dot) will not support downloads to a Logic Solver. The earliest MD Controllers will not support the DeltaV SIS system. The MD controllers must have a part number 12P2093X082 or higher.
Recommended models
EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON EMERSON | PR6426/000-131 CON041 1X00691H01 1X00884H01 775XD11NAWA3WK9 W74C5X1 MMS6110 KJ3222X1-BA1 12P2532X072 VE4033S2B1 KC3010X1-BA1 12P6762X062 KC3011X1-BA1 12P6749X042 KJ3001X1-BH1 12P0558X152 PR6423/002-121 CON041 KJ1501X1-BC1 12P2186X032 VE5008 KJ3221X1-BA1 12P2531X102 VE4035S2B1 KJ3002X1-BA1 12P0680X072 VE4003S2B2 KJ2002X1-BA1 12P1442X042 VE3002 KJ4001X1-BE1 12P0818X072 R6423/010-010 CON021 PR6423/00R-111-CN CON041 KJ3201X1-BA1 12P2535X052 KJ2201X1-JA1 12P3323X022 KJ2201X1-BA1 12P3162X162 VS3202 KJ3202X1-BA1 12P2536X042 VE4032S1T2B1 KJ4001X1-JA1 12P1832X022 KJ3002X1-BC1 12P0681X072 VE4003S1B2 KJ3002X1-BC1 12P0681X082 VE4003S1B2 | Eddy Current Sensor Ovation PMOD Cavity Plastic Insert Compact Controller Wireless Adapter Signal Transfer Board Relative rotor vibration monitor Analog Input Traditional I/O Analog Module Isolated Card Current Sensor Power Supply Electronic Unit Controller CONTROLLER I/O Carrier with Shield Bar Eddy Current Sensor Eddy Current Sensor Isolated Card Terminal Block Logic Solver DeltaV Discrete Output Card Terminal Block Analog Input Analog Input Module |
Contact Us: Email:sales@sparecenter.com