Product Specification
Product Specification | Product Image | |
---|---|---|
Manufacturer | YOKOGAWA | ![]() |
Product No. | SDV541-S63 S3 | |
Number of input channels | Digital Output Module | |
Number of outputs | 16-channel, module isolation (*3) | |
Output voltage | 24 V DC | |
Output voltage drop | 1 V maximum | |
External power supply rating | 24 V DC, 3.4 A minimum | |
External power supply | 24 V DC + 20 % / -10 % (*4) Current capacity: 3.4 A | |
Maximum leak current at output off status | 1.6 mA | |
Output format | Current source | |
Maximum load current | 0.2 A/output line (3.2 A in total output line) (*3) (*5) | |
Minimum load current | 35 mA | |
Load resistance range | 120 to 685 Ω (*6) |
Details of YOKOGAWA SDV541-S63 S3
MORE TECHNICAL DATA
Output response time:30 ms maximum
Withstand voltage (*1) (*2):2 kV AC between output signal lines and system for 1 minute, 16-point input lines collectively connected (negative lines) (*7)
Current consumption:300 mA maximum (5 V DC) 150 mA maximum (24 V DC)
Weight:Approx. 0.29 kg (For pressure clamp terminal block or MIL cable) Approx. 0.31 kg (With dedicated signal cable interface adapter)
FEATURE
16 Channels: Provides 16 digital output channels for versatile control and signal distribution.
24 V DC Output: Delivers reliable 24 V DC outputs suitable for various industrial applications.
Module Isolation: Features isolation to protect against electrical noise and ensure signal integrity.
Application
Industrial Automation: Controls various actuators, relays, and devices in automated production lines and machinery.
Process Control Systems: Outputs control signals to field devices, ensuring accurate process regulation and control.
Building Management Systems: Manages outputs for HVAC systems, lighting controls, and other building systems.
If you want to more details,please contact me without hesitate.Email:sales@sparecenter.com
Graph And Figure of YOKOGAWA SDV541-S63 S3
![]() |
Terminal Board is Connected The SDV541 digital output module can respectively handle a maximum of 0.2 A load currents per channel. However, this can cause the generation of a voltage drop due to connected cable and adapter resistance components, etc. Therefore, it is necessary to take account of the limitations on the magnitude of load current and connected cable length as given below. In case of short circuits detection is enabled, the possible cable length may be limited. |
Our Advantage
Fast Shipping
We guarantee prompt shipping to ensure you receive your product as quickly as possible, minimizing downtime and production delays.
One-Year Warranty
All our products come with a one-year warranty, providing reliable after-sales support and peace of mind.
High Customer Satisfaction
We are committed to delivering exceptional customer service, ensuring a smooth purchasing experience and effective solutions.
Other Modules
YOKOGAWAECO*ASignal Conditioner YOKOGAWAMX2*DMultiplexer Card YOKOGAWA SCP461-51 S2 YOKOGAWA SCP461-51 S2 YOKOGAWASDV144-S33Digital Input Module YOKOGAWA SDV541-S63 S3 YOKOGAWA SDV541-S63 S3 YOKOGAWA SDV541-S63 S3 YOKOGAWAAIP532 S1V-Net Coupler Module YOKOGAWA SCP461-51 S2 YOKOGAWA SCP461-51 S2 YOKOGAWAPW302 S4Power Supply YOKOGAWASAI143-S63ProSafe-RS Analog Module YOKOGAWA Digital Output Module SDV541-S63 SDV541-S63 YOKOGAWA SDV541-S63 S3 YOKOGAWA SDV541-S63 S3 YOKOGAWAAMM52 S4Processor Module YOKOGAWA Processor Module YOKOGAWA Processor Module SCP461-51 YOKOGAWASAI533-H33/PRP S1Analog Output Module YOKOGAWACP11*C AS S9291AS-0CPU Module YOKOGAWA Digital Output Module YOKOGAWA Digital Output Module SDV541-S63 S3 YOKOGAWA Digital Output Module SDV541-S63 SDV541-S63 YOKOGAWAEH1*AInput Card YOKOGAWAER5*BRTD Input Card YOKOGAWAER5*CInput Card YOKOGAWAET5*BInput Card YOKOGAWAEXT*ATemperature Transmitter YOKOGAWAMX3*DI/O Card |
Mobile/what's app: +852 6980 6006