Product Specification
Parameter | Specification | Paramater | Specification |
---|---|---|---|
Manufacturer | Honeywell | Temperature stability | TC, Millivoltage input +/-20 ppm per deg C max RTD inputs +/-20 ppm per deg C max |
Product No. | LLMUX2 | Long term drift | 500 ppm |
Input channels | 16 fully-isolated channel-to-channel, channel-to-PM, and channel-to-power supply common | Input impedance | 1 megohm at dc (TC only) |
Origin of Country | USA | CMV with respect to PM common, dc to 60 Hz | +/-250 Vdc or Vac rms |
Channel bandwidth | 0 to 4.7 Hz (-3 dB) | CMRR, 50 or 60 Hz (with 1000 ohms source impedance max.) | 120 dB min |
Input scan rate | 1 Second fixed by IOLP | Voltage, channel-to-channel, dc to 60 Hz | +/-250 Vdc or Vac rms |
Nominal input range (TC only) | -20 to +100 millivolts | Crosstalk, dc to 60 Hz | 80 dB (120 dB at 50 and 60 Hz) |
Maximum normal mode continuous input non-damaging (any thermocouple type configured) | -10 to +10 volts (TC) -1 to +2 Volts @ 100 milliamps (RTD) | NMRR at 60 Hz | 60 dB min |
Gain error (-20 to +100 millivolt range) | 0.050% full scale max | NMRR at 50 Hz | 60 dB min |
Resolution of reading | Type TC 2 microvolt per bit RTD 8 milliohm per bit Millivolt 2 microvolt per bit | Line frequency integration | Fixed selection of 50 Hz or 60 Hz |
HONEYWELL LLMUX2 Details
1
Description
The LLMUX2 Honeywell TC and RTD FTAs are cutting-edge field termination assemblies designed for precise temperature measurement. They feature separate A/D converters per channel, improved open thermocouple detection, and enhanced loop resistance for longer wiring. Ideal for new installations, upgrades, or replacements, these FTAs leverage solid-state technology for reliability and include on-board diagnostics for efficient monitoring.
2
Feature
Separate A/D Converters: Each channel has its own analog-to-digital converter for improved accuracy and response times.
Enhanced Thermocouple Detection: Improved open thermocouple detection capabilities within one second for faster diagnostics.
Longer Wiring Support: Enhanced loop resistance allows for longer thermocouple wiring without loss of signal integrity.
3
Application
Industrial Process Control: Ideal for monitoring and controlling temperature in manufacturing processes across industries like oil and gas, chemicals, and pharmaceuticals.
Power Generation: Used in power plants for temperature monitoring of critical equipment, ensuring efficient operation and safety.
If you want to more details,please contact me without hesitate.Email:sales@sparecenter.com
Graphs And Figures of HONEYWELL LLMUX2
![]() |
Figure: below shows the cable interconnections between the Remote CJR and the LLMUX2 TC FTA. |
Product Images
![]() | ![]() | ![]() |
Other Modules
HONEYWELL10201/2/1 FC-SDO-0824Digital Output Module HONEYWELL51403988-150High Performance Process Manager Comm Controller HONEYWELL80363972-150Digital Input 24 Vdc Processor HONEYWELL05704-A-0121Quad Relay Interface Card HONEYWELL51402573-150HPM UCN Interface HONEYWELL51109693-100BGround Tap HONEYWELL51195153-001COAXIAL DROP CABLE RG6 1M 75OHM HONEYWELL51305430-100PC BOARD LCNP-4 HONEYWELLTK-OAV061Analog Output Module MC-TAMT04 MC-TAMT04 MC-TAMT04 MC-TAMT04 LLMUX2 LLMUX2 LLMUX2 LLMUX2 HONEYWELLFTA-T-08Fail-safe digital output module Honeywell MC-TAMT04 Honeywell MC-TAMT04 Honeywell MC-TAMT04 MC-TAMT04 MC-TAMT04 MC-TAMT04 MC-TAMT04 LLMUX2 LLMUX2 LLMUX2 LLMUX2 Honeywell LLMUX2 Honeywell LLMUX2 Honeywell LLMUX2 Honeywell LLMUX2 Honeywell LLMUX2 Honeywell LLMUX2 Honeywell LLMUX2 Honeywell LLMUX2 HONEYWELL TC and RTD FTAs HONEYWELL TC and RTD FTAs HONEYWELL TC and RTD FTAs Honeywell MC-TAMT04 Honeywell MC-TAMT04 Honeywell MC-TAMT04 Honeywell MC-TAMT04 Honeywell Serial Interface Modbus Honeywell Serial Interface Modbus Honeywell 51303932-476 Honeywell 51303932-476 Honeywell 51303932-476 |